The SEC3016C Conventional Fire Alarm Control Panel is a versatile and reliable solution designed for small to medium-sized applications. Supporting multiple zone configurations and up to 32 devices per zone, the panel offers flexible system design while simplifying installation through its two-wire architecture. Four sounder outputs, repeater communication support, and EN 54 compliance provide dependable alarm management for a wide range of facilities.
- Model
- SEC3016C
- Product number
- 8
Key features
- Available in 2, 4, 8, 12, and 16 zone configurations.
- Supports up to 32 devices per zone.
- Walk test function.
- Zone and sounder disablement facility.
- Supports batteries up to 7Ah.
- Sounder delay option.
- Four sounder circuits.
- Two sounder circuits configurable as auxiliary 24V outputs.
- Repeater communication interface support.
- Simplified two-wire system architecture.
- Compliant with EN 54-2 and EN 54-4.
Technical specifications
| Model | SEC3016C |
|---|---|
| Product Type | Conventional Fire Alarm Control Panel |
| Standards | EN 54-2 & EN 54-4 |
| Zone Configurations | 2 / 4 / 8 / 12 / 16 Zones |
| Zone Capacity | Up to 32 Devices per Zone |
| Mains Supply | 110/230V AC (-15%, +10%), 50Hz/60Hz |
| Power Supply Rating | 26.5V–28.5V DC ±0.5V |
| Battery Charge Current | 0.4A Max |
| Recommend Battery | 7Ah VRLA (NP7-12 Yuasa) |
| Battery Fuse | 3A |
| Max Internal Battery Resistance | 1.5Ω |
| Quiescent Current | ≤0.1A |
| Zone Voltage | 20V–28V DC |
| Zone Alarm Current Threshold | 15mA |
| Sounder Alarm Outputs | 4 × 150mA @ 24V DC |
| Sounder End of Line | 10KΩ, 1W |
| Fire Relay | 1 × Volt Free Relay, 2A @ 30V DC Max |
| Fault Relay | 1 × Volt Free Relay, 2A @ 30V DC Max |
| Construction | 1.0mm Mild Sheet Steel |
| Flame Retardant Rating | V2 |
| IP Rating | IP30 |
| Dimensions (W×H×D) | 380 × 340 × 105 mm |
| Weight (Without Battery) | 5 kg |
| Operating Temperature | -10°C to +55°C |
| Relative Humidity | 95% (Non-Condensing) |