Conventional Fire Alarm Control Panel

The SEC3016C Conventional Fire Alarm Control Panel is a versatile and reliable solution designed for small to medium-sized applications. Supporting multiple zone configurations and up to 32 devices per zone, the panel offers flexible system design while simplifying installation through its two-wire architecture. Four sounder outputs, repeater communication support, and EN 54 compliance provide dependable alarm management for a wide range of facilities.

Model
SEC3016C
Product number
8

Key features

  • Available in 2, 4, 8, 12, and 16 zone configurations.
  • Supports up to 32 devices per zone.
  • Walk test function.
  • Zone and sounder disablement facility.
  • Supports batteries up to 7Ah.
  • Sounder delay option.
  • Four sounder circuits.
  • Two sounder circuits configurable as auxiliary 24V outputs.
  • Repeater communication interface support.
  • Simplified two-wire system architecture.
  • Compliant with EN 54-2 and EN 54-4.

Technical specifications

Model SEC3016C
Product Type Conventional Fire Alarm Control Panel
Standards EN 54-2 & EN 54-4
Zone Configurations 2 / 4 / 8 / 12 / 16 Zones
Zone Capacity Up to 32 Devices per Zone
Mains Supply 110/230V AC (-15%, +10%), 50Hz/60Hz
Power Supply Rating 26.5V–28.5V DC ±0.5V
Battery Charge Current 0.4A Max
Recommend Battery 7Ah VRLA (NP7-12 Yuasa)
Battery Fuse 3A
Max Internal Battery Resistance 1.5Ω
Quiescent Current ≤0.1A
Zone Voltage 20V–28V DC
Zone Alarm Current Threshold 15mA
Sounder Alarm Outputs 4 × 150mA @ 24V DC
Sounder End of Line 10KΩ, 1W
Fire Relay 1 × Volt Free Relay, 2A @ 30V DC Max
Fault Relay 1 × Volt Free Relay, 2A @ 30V DC Max
Construction 1.0mm Mild Sheet Steel
Flame Retardant Rating V2
IP Rating IP30
Dimensions (W×H×D) 380 × 340 × 105 mm
Weight (Without Battery) 5 kg
Operating Temperature -10°C to +55°C
Relative Humidity 95% (Non-Condensing)